EICR Electrical Inspections

An EICR records the condition of an electrical installation at the time of inspection. Provide the property type, approximate size, reason for the report and preferred timing so Big Volt Electric can confirm availability, scope and the information needed.

When to enquire

This service may be relevant for

  • Landlords arranging periodic electrical checks
  • Home buyers or owners seeking information about an installation
  • Property managers coordinating access and documentation
  • Clients responding to a recommendation for further inspection

Define the scope

Points to confirm in writing

  • Confirmation of the property and inspection requirements
  • An agreed inspection scope before attendance
  • A report recording the findings of the inspection
  • A clear route for discussing any observations or next steps

Enquiry process

A practical route to an agreed job

  1. 01

    Share the property type, size, postcode and reason for the report.

  2. 02

    We confirm access requirements, scope and availability.

  3. 03

    The inspection is arranged with the responsible contact.

  4. 04

    The report and any recommended next steps are provided after the inspection.

What an inspection covers

What an EICR tests, and what the result means

An Electrical Installation Condition Report records the condition of the fixed wiring at the time of inspection. It combines visual inspection with electrical testing — insulation resistance, earth fault loop impedance, continuity, polarity and RCD operation — and results in a report that is either satisfactory or unsatisfactory, with observations coded.

It covers the fixed installation: the board, circuits, sockets, switches and fittings. It does not cover plug-in appliances, which is a separate exercise. Power is off for the dead testing and restored for live testing, and accessories are opened and sampled, so access matters.

The codes

C1 means danger present and immediate action required. C2 means potentially dangerous and urgent remedial action required. C3 is improvement recommended and does not fail a report. FI means further investigation required. Any C1, C2 or FI makes the report unsatisfactory.

Limitations

Every report states the agreed extent and any limitations — areas not accessed, fittings not opened, or a sampling percentage. Read this section: a report with heavy limitations tells you much less than one without.

Frequency

The widely used guidance is at least every ten years for an owner-occupied home and every five years for rented property, or at a change of occupancy. The recommended next date is stated on the report itself.

Access

Clear access to the consumer unit and to accessories behind furniture makes a material difference. Anything that cannot be reached has to be recorded as a limitation.

Questions about eicr inspections

The property type, approximate number of bedrooms, postcode, occupancy status, reason for the report and any previous electrical documents are useful starting points.